| Technical data |
|
| Supply voltage |
DC5V ±5% |
| Current consumption |
600mA |
| Potential separation |
yes |
| Number of inputs |
16 voltage/current inputs referred to ground |
| Measured value representation |
13-bit (complement or two) or 12-bit with sign |
| |
±2048 units within nominal range |
| |
512 to 2560 units at 4…20mA |
| Integration time switchable: |
|
| - for fast measurement acquisition |
0.4msec |
| - max. interference suppression |
20msec at 50Hz; 16msec at 60Hz |
| Ready delay time |
10µsec |
| Input resistance |
all voltage ranges 10kOhm |
| |
all current ranges 125 Ohm |
| Error message |
at overflow |
| max. input voltage |
±15V referred to analog ground |
| max. input current |
±50mA referred to analog ground |
| Measurement accuracy at 20°C |
linearity ±1 unit |
| |
tolerance ±2 units |
| |
|
| Dimensions and weight |
|
| Height |
233.4 mm |
| Depth |
160.0 mm |
| Weight |
ca. 460 gr |
| |
|
| Ambient Conditions |
|
| Operating temp. |
0°C..+.55°C |
| Storage temp. |
-20°C…+70°C |
| Relative humidity |
95% no condensation |
| No forced ventilation |
|
| Space requirements |
1 slot |
| |
|