Back


    TB20-C Modbus TCP Slave
    Part No: 600-170-1AA11
    .
    TB20-C Modbus TCP Slave head for TB20 I/O system

    Includes internal Power module
    Up to 64 modules per rack (Siemens ET200S only allows 12)
    Hotswap module capable
    Free Software Toolbox for simulation and diagnosis in addition to information available from Siemens STEP7 / TIA Portal, or WinPLC7 software.
    Detailed status indication of all modules in use in the system
    Fault Tracking and fault repair
    Galvanic isolation between fieldbus and backplane bus


    TB20-C, Bus Coupler MODBUS TCP

    The ModbusTCP bus coupler makes it possible to access data from peripheral modules using the ModbusTCP protocol, but can accommodate up to 64 modules of any kind connected in series with the bus coupler.
    The ModbusTCP bus coupler features an integrated two-port switch that allows for star and line topology configurations.
    A large I/O image table size of 2 kbytes makes it possible to implement comprehensive and complex systems.
    The control and status registers can be used to configure and monitor the coupler's behavior with ModbusTCP.
    TB20 ToolBox can be used to easily configure the system structure and the various module parameters, and transfer the corresponding settings to the coupler.
    A functioning TB20 configuration will always require a bus coupler and at least one peripheral module. The bus coupler supports hot-swapping for replacing modules during operation. .

    This bus coupler will make it possible to run a distributed I/O station with nothing more than an Ethernet cable.

    Note:
    The 24 V power supply connector, the final bus cover, and the base module are included as standard.
    TB20 ToolBox makes it easy to methodically design TB20 systems. Integrated terminal mapping, system width calculations, and Current-carrying capacity monitoring all make it possible to quickly design systems without making any mistakes.

    Characteristics
    • Modules can be replaced during operation (hot-swapping)
    • 24 V DC power supply
    • Integrated power supply unit for powering peripheral modules (2.5 A)
    • Supplies the system’s I/O voltage (24 VDC)
    • USB device port for online diagnostics, configuring parameters, setup, and firmware updates with TB20 ToolBox
    • TB20 ToolBox simulation for commissioning the I/O system without a higher-level controller in order to test the functionality (I/O check)
    • Concealed "factory reset" switch for restoring the module to its factory settings
    • Connection watchdog for connection monitoring
    • Simultaneous access to up to 10 stations (TCP connections)
    • Integrated two-port switch
    • Up to 64 peripheral modules
    • 2 x RJ45 connections
    • 2048 bytes of input, 2048 bytes of output data
    • 126 bytes of parameter data per module
    • The coupler's behavior can be configured using control registers
    • The coupler's status can be read out using status registers
    • 7 LEDs, one of them bi-color



  • Please Sign In for Pricing