Back


    SPEED7 317SN EtherCAT -2Mb
    Part No: VIPA 317-4EC12
    .
    CPU 317SN/EC EtherCAT – SPEED7 Technology
    Programmed by STEP7 from Siemens or WinPLC7 from VIPA
    DC 24V
    2MByte memory expandable to 8MByte (50% program + 50% data)
    MPI interface, 187.5 to 12Mb
    MMC slot,
    real time clock,
    8192/8192byte I/O address area
    2048 timers (IEC timers unlimited)
    2048 Counters (IEC Counters unlimited)
    16384 flag byte
    Firmware upgrade via MMC
    Ethernet interface for PG/OP communication
    Profibus-DP master, 12MBaud, up to 126 slaves,
    As well as the standard function of the DP Master/slave port the CPU 317-4EC12 offers a extra mode of switchable RS485 interface for PtP communication with Modbus and other serial protocols.
    Extra to the 24 standard Ethernet PG/OP channels, this CPU 317-4EC12 integrates the additional (2x TCP ports) CP343 Ethernet interface for up to 24 TCP connections and 512 EtherCAT Slave device connections.
    VIPA SPEED7 EtherCAT Manager software required
    TCP/IP and S7-communication

    The new SPEED7 CPU's from VIPA are the fastest PLC in the world, more than 10x faster than the Siemens S7-400 CPU's the VIPA SPEED7 can handle the biggest applications. The memory is not fixed in size, it is expandable by purchasing a MMC memory upgrade, so your plant cost life cycle is reduced.

    Click for Features Matrix

    FeaturesSPEED7 technology, SPEED-Bus
    2 MB work memory
    Memory extension (max. 8 MB)
    PROFIBUS-DP master / PtP (switchable)
    EtherCAT-Master integrated
    SPEED-Bus
    Technical data power supply
    Power supply (rated value)DC 24 V
    Power supply (permitted range)DC 20.4...28.8 V
    Reverse polarity protection
    Current consumption (no-load operation)270 mA
    Current consumption (rated value)1.5 A
    Inrush current6 A
    I²t0.28 A²s
    Max. current drain at backplane bus3 A
    Max. current drain load supply-
    Power loss10 W
    Load and working memory
    Load memory, integrated8 MB
    Load memory, maximum8 MB
    Work memory, integrated2 MB
    Work memory, maximal8 MB
    Memory divided in 50% program / 50% data
    Memory card slotMMC-Card with max. 1 GB
    Hardware configuration
    Racks, max.4
    Modules per rack, max.8 in multiple-, 32 in a single-rack configuration
    Number of integrated DP master1
    Number of DP master via CP4
    Operable function modules8
    Operable communication modules PtP16
    Operable communication modules LAN8
    Command processing times
    Bit instructions, min.0.01 µs
    Word instruction, min.0.01 µs
    Double integer arithmetic, min.0.01 µs
    Floating-point arithmetic, min.0.06 µs
    Timers/Counters and their retentive characteristics
    Number of S7 counters2048
    S7 counter remanenceadjustable 0 up to 2048
    S7 counter remanence adjustableC0 .. C7
    Number of S7 times2048
    S7 times remanenceadjustable 0 up to 2048
    S7 times remanence adjustablenot retentive
    Data range and retentive characteristic
    Number of flags16384 Byte
    Bit memories retentive characteristic adjustableadjustable 0 up to 16384
    Bit memories retentive characteristic presetMB0 .. MB15
    Number of data blocks8190
    Max. data blocks size64 KB
    Number range DBs1 ... 8190
    Max. local data size per execution level3072 Byte
    Max. local data size per block3072 Byte
    Blocks
    Number of OBs24
    Maximum OB size64 KB
    Total number DBs, FBs, FCs-
    Number of FBs8191
    Maximum FB size64 KB
    Number range FBs0 ... 8190
    Number of FCs8191
    Maximum FC size64 KB
    Number range FCs0 ... 8190
    Maximum nesting depth per priority class16
    Maximum nesting depth additional within an error OB4
    Time
    Real-time clock buffered
    Clock buffered period (min.)6 w
    Type of bufferingVanadium Rechargeable Lithium Battery
    Load time for 50% buffering period20 h
    Load time for 100% buffering period48 h
    Accuracy (max. deviation per day)10 s
    Number of operating hours counter8
    Clock syncbonization
    Syncbonization via MPIMaster/Slave
    Syncbonization via Ethernet (NTP)Slave
    Address areas (I/O)
    Input I/O address area8192 Byte
    Output I/O address area8192 Byte
    Process image adjustable
    Input process image preset256 Byte
    Output process image preset256 Byte
    Input process image maximal8192 Byte
    Output process image maximal8192 Byte
    Digital inputs65536
    Digital outputs65536
    Digital inputs central1024
    Digital outputs central1024
    Integrated digital inputs-
    Integrated digital outputs-
    Analog inputs4096
    Analog outputs4096
    Analog inputs, central256
    Analog outputs, central256
    Integrated analog inputs-
    Integrated analog outputs-
    Communication functions
    PG/OP channel
    Global data communication
    Number of GD circuits, max.8
    Size of GD packets, max.22 Byte
    S7 basic communication
    S7 basic communication, user data per job76 Byte
    S7 communication
    S7 communication as server
    S7 communication as client-
    S7 communication, user data per job160 Byte
    Number of connections, max.32
    Functionality Sub-D interfaces
    TypeX2
    Type of interfaceRS485
    ConnectorSub-D, 9-pin, female
    Electrically isolated
    MPI
    MP²I (MPI/RS232)-
    DP master-
    DP slave-
    Point-to-point interface-
    TypeX3
    Type of interfaceRS485
    ConnectorSub-D, 9-pin, female
    Electrically isolated
    MPI-
    MP²I (MPI/RS232)-
    DP masteryes
    DP slaveyes
    Point-to-point interface
    Functionality MPI
    Number of connections, max.32
    PG/OP channel
    Routing
    Global data communication
    S7 basic communication
    S7 communication
    S7 communication as server
    S7 communication as client-
    Transmission speed, min.19.2 kbit/s
    Transmission speed, max.12 Mbit/s
    Functionality PROFIBUS master
    PG/OP channel
    Routing
    S7 basic communication
    S7 communication
    S7 communication as server
    S7 communication as client-
    Activation/deactivation of DP slaves
    Direct data exchange (slave-to-slave communication)-
    DPV1
    Transmission speed, min.9.6 kbit/s
    Transmission speed, max.12 Mbit/s
    Number of DP slaves, max.124
    Address range inputs, max.8 KB
    Address range outputs, max.8 KB
    User data inputs per slave, max.244 Byte
    User data outputs per slave, max.244 Byte
    Functionality PROFIBUS slave
    PG/OP channel
    Routing
    S7 communication
    S7 communication as server
    S7 communication as client-
    Direct data exchange (slave-to-slave communication)-
    DPV1
    Transmission speed, min.9.6 kbit/s
    Transmission speed, max.12 Mbit/s
    Automatic detection of transmission speed-
    Transfer memory inputs, max.244 Byte
    Transfer memory outputs, max.244 Byte
    Address areas, max.32
    User data per address area, max.32 Byte
    Point-to-point communication
    PtP communication
    Interface isolated
    RS232 interface-
    RS422 interface-
    RS485 interface
    ConnectorSub-D, 9-pin, female
    Transmission speed, min.1200 bit/s
    Transmission speed, max.115.5 kbit/s
    Cable length, max.500 m
    Point-to-point protocol
    ASCII protocol
    STX/ETX protocol
    3964(R) protocol
    RK512 protocol-
    USS master protocol
    Modbus master protocol
    Modbus slave protocol-
    Special protocols-
    Functionality RJ45 interfaces
    TypeX5
    Type of interfaceEthernet 10/100 MBit
    ConnectorRJ45
    Electrically isolated
    PG/OP channel
    Number of connections, max.4
    Productive connections-
    TypeX8
    Type of interfaceEthernet 10/100 MBit
    ConnectorRJ45
    Electrically isolated
    PG/OP channel
    Number of connections, max.8
    Productive connections
    Ethernet communication CP
    Number of productive connections, max.24
    Number of productive connections by Siemens NetPro, max.16
    S7 connectionsBSEND, BRCV, GET, PUT, Connection of active and passive data handling
    User data per S7 connection, max.32 KB
    TCP-connectionsFETCH PASSIV, WRITE PASSIV, Connection of passive data handling
    User data per TCP connection, max.64 KB
    ISO-connections-
    User data per ISO connection, max.-
    ISO on TCP connections (RFC 1006)FETCH PASSIV, WRITE PASSIV, Connection of passive data handling
    User data per ISO on TCP connection, max.32 KB
    UDP-connections-
    User data per UDP connection, max.-
    UDP-multicast-connections-
    UDP-broadcast-connections-
    Ethernet open communication
    Number of connections, max.24
    User data per ISO on TCP connection, max.8 KB
    User data per native TCP connection, max.8 KB
    User data per ad hoc TCP connection, max.1460 Byte
    User data per UDP connection, max.1472 Byte
    EtherCAT Master
    Number of EtherCAT-slaves512
    Update time500 µs .. 512 ms
    Address range inputs, max.4 KB
    Address range outputs, max.4 KB
    EoE support
    FoE support
    Distributed Clock support
    Hotconnect Slaves
    Isocbonous mode-
    Management & diagnosis
    ProtocolsICMP
    LLC
    Web based diagnosis-
    NCM diagnosis
    Housing
    MaterialPPE
    MountingRail System 300
    Mechanical data
    Dimensions (WxHxD)80 mm x 125 mm x 120 mm
    Weight440 g
    Environmental conditions
    Operating temperature0 °C to 60 °C
    Storage temperature-25 °C to 70 °C
    Certifications
    UL certificationin preparation

  • Please Sign In for Pricing