SPEED7 315SN EtherCAT -1Mb
Part No: VIPA 315-4EC12
.
CPU 315SN/EC EtherCAT – SPEED7 Technology
Programmed by STEP7 from Siemens or WinPLC7 from VIPA
DC 24V
1MByte memory expandable to 2MByte (50% program + 50% data)
MPI interface, 187.5 to 12Mb
MMC slot,
real time clock,
2048/2048byte I/O address area
512 timers (IEC timers unlimited)
512 Counters (IEC Counters unlimited)
8192 flag byte
Firmware upgrade via MMC
Ethernet interface for PG/OP communication
Profibus-DP master, 12MBaud, up to 126 slaves,
As well as the standard function of the DP Master/slave port the CPU 315-4EC12 offers a extra mode of switchable RS485 interface for PtP
communication with Modbus and other serial protocols.
Extra to the 8 standard Ethernet PG/OP channels,
this CPU 315-4EC12 integrates the additional (2x TCP ports) CP343 Ethernet interface for up to 8 TCP connections and 128 EtherCAT Slave device connections.
VIPA SPEED7 EtherCAT Manager software required
TCP/IP and S7-communication
The new SPEED7 CPU's from VIPA are the fastest PLC in the world, more than 10x faster than the Siemens S7-400 CPU's the VIPA SPEED7 can handle the biggest applications. The memory is not fixed in size, it is expandable by purchasing a MMC memory upgrade, so your plant cost life cycle is reduced.
Click for Features Matrix
| Features | SPEED7 technology 1 MB work memory Memory extension (max. 2 MB) PROFIBUS-DP master / PtP (switchable) EtherCAT controller integrated |
| SPEED-Bus | - |
| Technical data power supply | |
| Power supply (rated value) | DC 24 V |
| Power supply (permitted range) | DC 20.4...28.8 V |
| Reverse polarity protection | ![]() |
| Current consumption (no-load operation) | 270 mA |
| Current consumption (rated value) | 1.1 A |
| Inrush current | 6 A |
| I²t | 0.28 A²s |
| Max. current drain at backplane bus | 2.5 A |
| Max. current drain load supply | - |
| Power loss | 8.5 W |
| Load and working memory | |
| Load memory, integrated | 2 MB |
| Load memory, maximum | 2 MB |
| Work memory, integrated | 1 MB |
| Work memory, maximal | 2 MB |
| Memory divided in 50% program / 50% data | ![]() |
| Memory card slot | MMC-Card with max. 1 GB |
| Hardware configuration | |
| Racks, max. | 4 |
| Modules per rack, max. | 8 in multiple-, 32 in a single-rack configuration |
| Number of integrated DP master | 1 |
| Number of DP master via CP | 4 |
| Operable function modules | 8 |
| Operable communication modules PtP | 8 |
| Operable communication modules LAN | 8 |
| Command processing times | |
| Bit instructions, min. | 0.01 µs |
| Word instruction, min. | 0.01 µs |
| Double integer arithmetic, min. | 0.01 µs |
| Floating-point arithmetic, min. | 0.06 µs |
| Timers/Counters and their retentive characteristics | |
| Number of S7 counters | 512 |
| S7 counter remanence | adjustable 0 up to 512 |
| S7 counter remanence adjustable | C0 .. C7 |
| Number of S7 times | 512 |
| S7 times remanence | adjustable 0 up to 512 |
| S7 times remanence adjustable | not retentive |
| Data range and retentive characteristic | |
| Number of flags | 8192 Byte |
| Bit memories retentive characteristic adjustable | adjustable 0 up to 8192 |
| Bit memories retentive characteristic preset | MB0 .. MB15 |
| Number of data blocks | 4095 |
| Max. data blocks size | 64 KB |
| Number range DBs | 1 ... 4095 |
| Max. local data size per execution level | 3072 Byte |
| Max. local data size per block | 3072 Byte |
| Blocks | |
| Number of OBs | 24 |
| Maximum OB size | 64 KB |
| Total number DBs, FBs, FCs | - |
| Number of FBs | 2048 |
| Maximum FB size | 64 KB |
| Number range FBs | 0 ... 2047 |
| Number of FCs | 2048 |
| Maximum FC size | 64 KB |
| Number range FCs | 0 ... 2047 |
| Maximum nesting depth per priority class | 8 |
| Maximum nesting depth additional within an error OB | 4 |
| Time | |
| Real-time clock buffered | ![]() |
| Clock buffered period (min.) | 6 w |
| Type of buffering | Vanadium Rechargeable Lithium Battery |
| Load time for 50% buffering period | 20 h |
| Load time for 100% buffering period | 48 h |
| Accuracy (max. deviation per day) | 10 s |
| Number of operating hours counter | 8 |
| Clock synchronization | ![]() |
| Synchronization via MPI | Master/Slave |
| Synchronization via Ethernet (NTP) | Slave |
| Address areas (I/O) | |
| Input I/O address area | 2048 Byte |
| Output I/O address area | 2048 Byte |
| Process image adjustable | ![]() |
| Input process image preset | 128 Byte |
| Output process image preset | 128 Byte |
| Input process image maximal | 2048 Byte |
| Output process image maximal | 2048 Byte |
| Digital inputs | 16384 |
| Digital outputs | 16384 |
| Digital inputs central | 1024 |
| Digital outputs central | 1024 |
| Integrated digital inputs | - |
| Integrated digital outputs | - |
| Analog inputs | 1024 |
| Analog outputs | 1024 |
| Analog inputs, central | 256 |
| Analog outputs, central | 256 |
| Integrated analog inputs | - |
| Integrated analog outputs | - |
| Communication functions | |
| PG/OP channel | ![]() |
| Global data communication | ![]() |
| Number of GD circuits, max. | 8 |
| Size of GD packets, max. | 22 Byte |
| S7 basic communication | ![]() |
| S7 basic communication, user data per job | 76 Byte |
| S7 communication | ![]() |
| S7 communication as server | ![]() |
| S7 communication as client | - |
| S7 communication, user data per job | 160 Byte |
| Number of connections, max. | 32 |
| Functionality Sub-D interfaces | |
| Type | X2 |
| Type of interface | RS485 |
| Connector | Sub-D, 9-pin, female |
| Electrically isolated | ![]() |
| MPI | ![]() |
| MP²I (MPI/RS232) | - |
| DP master | - |
| DP slave | - |
| Point-to-point interface | - |
| Type | X3 |
| Type of interface | RS485 |
| Connector | Sub-D, 9-pin, female |
| Electrically isolated | ![]() |
| MPI | - |
| MP²I (MPI/RS232) | - |
| DP master | yes |
| DP slave | yes |
| Point-to-point interface | ![]() |
| Functionality MPI | |
| Number of connections, max. | 32 |
| PG/OP channel | ![]() |
| Routing | ![]() |
| Global data communication | ![]() |
| S7 basic communication | ![]() |
| S7 communication | ![]() |
| S7 communication as server | ![]() |
| S7 communication as client | - |
| Transmission speed, min. | 19.2 kbit/s |
| Transmission speed, max. | 12 Mbit/s |
| Functionality PROFIBUS master | |
| PG/OP channel | ![]() |
| Routing | ![]() |
| S7 basic communication | ![]() |
| S7 communication | ![]() |
| S7 communication as server | ![]() |
| S7 communication as client | - |
| Activation/deactivation of DP slaves | ![]() |
| Direct data exchange (slave-to-slave communication) | - |
| DPV1 | ![]() |
| Transmission speed, min. | 9.6 kbit/s |
| Transmission speed, max. | 12 Mbit/s |
| Number of DP slaves, max. | 124 |
| Address range inputs, max. | 8 KB |
| Address range outputs, max. | 8 KB |
| User data inputs per slave, max. | 244 Byte |
| User data outputs per slave, max. | 244 Byte |
| Functionality PROFIBUS slave | |
| PG/OP channel | ![]() |
| Routing | ![]() |
| S7 communication | ![]() |
| S7 communication as server | ![]() |
| S7 communication as client | - |
| Direct data exchange (slave-to-slave communication) | - |
| DPV1 | ![]() |
| Transmission speed, min. | 9.6 kbit/s |
| Transmission speed, max. | 12 Mbit/s |
| Automatic detection of transmission speed | - |
| Transfer memory inputs, max. | 244 Byte |
| Transfer memory outputs, max. | 244 Byte |
| Address areas, max. | 32 |
| User data per address area, max. | 32 Byte |
| Point-to-point communication | |
| PtP communication | ![]() |
| Interface isolated | ![]() |
| RS232 interface | - |
| RS422 interface | - |
| RS485 interface | ![]() |
| Connector | Sub-D, 9-pin, female |
| Transmission speed, min. | 1200 bit/s |
| Transmission speed, max. | 115.5 kbit/s |
| Cable length, max. | 500 m |
| Point-to-point protocol | |
| ASCII protocol | ![]() |
| STX/ETX protocol | ![]() |
| 3964(R) protocol | ![]() |
| RK512 protocol | - |
| USS master protocol | ![]() |
| Modbus master protocol | ![]() |
| Modbus slave protocol | - |
| Special protocols | - |
| Functionality RJ45 interfaces | |
| Type | X5 |
| Type of interface | Ethernet 10/100 MBit |
| Connector | RJ45 |
| Electrically isolated | ![]() |
| PG/OP channel | ![]() |
| Number of connections, max. | 4 |
| Productive connections | - |
| Type | X8 |
| Type of interface | Ethernet 10/100 MBit |
| Connector | RJ45 |
| Electrically isolated | ![]() |
| PG/OP channel | ![]() |
| Number of connections, max. | 8 |
| Productive connections | ![]() |
| Ethernet communication CP | |
| Number of productive connections, max. | 8 |
| Number of productive connections by Siemens NetPro, max. | 8 |
| S7 connections | BSEND, BRCV, GET, PUT, Connection of active and passive data handling |
| User data per S7 connection, max. | 32 KB |
| TCP-connections | FETCH PASSIV, WRITE PASSIV, Connection of passive data handling |
| User data per TCP connection, max. | 64 KB |
| ISO-connections | - |
| User data per ISO connection, max. | - |
| ISO on TCP connections (RFC 1006) | FETCH PASSIV, WRITE PASSIV, Connection of passive data handling |
| User data per ISO on TCP connection, max. | 32 KB |
| UDP-connections | - |
| User data per UDP connection, max. | - |
| UDP-multicast-connections | - |
| UDP-broadcast-connections | - |
| Ethernet open communication | |
| Number of connections, max. | 8 |
| User data per ISO on TCP connection, max. | 8 KB |
| User data per native TCP connection, max. | 8 KB |
| User data per ad hoc TCP connection, max. | 1460 Byte |
| User data per UDP connection, max. | 1472 Byte |
| EtherCAT Master | |
| Number of EtherCAT-slaves | 128 |
| Update time | 500 µs .. 512 ms |
| Address range inputs, max. | 2 KB |
| Address range outputs, max. | 2 KB |
| EoE support | ![]() |
| FoE support | ![]() |
| Distributed Clock support | ![]() |
| Hotconnect Slaves | ![]() |
| Isochronous mode | - |
| Management & diagnosis | |
| Protocols | ICMP LLC |
| Web based diagnosis | - |
| NCM diagnosis | ![]() |
| Housing | |
| Material | PPE |
| Mounting | Rail System 300 |
| Mechanical data | |
| Dimensions (WxHxD) | 80 mm x 125 mm x 120 mm |
| Weight | 430 g |
| Environmental conditions | |
| Operating temperature | 0 °C to 60 °C |
| Storage temperature | -25 °C to 70 °C |
| Certifications | |
| UL certification | in preparation |